Key Options
Samsung Electronics 8-7
How to set the key function of the outdoor unit (cont.)
䒲 AM080ί2606XV666
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Emergency operation
for compressor
malfunction
Individual0 0
0 0 Disabled (Factory default)
E560 will occur when all the
compressors are set as
malfunction state.
01Set compressor 1 as malfunction state
0 2Set compressor 2 as m
alfunction state
Capacity correction
for cooling
Main 0 1
0 0 7-9 (Factory default)
T
argeted evaporation temperature
[?C] (When low temperature value
is set, discharged air temperature
of the indoor unit will decrease)
01 5-7
0 2 9-11
0 3 10-12
0 4 11-13
05 12-14
06 13-15
Capcity correction for
heating
Main 0 2
00 3.0 (Factory default)
T
argeted high pressure [MPa]
(When low pressure value is set,
discharged air temperature of the
indoor unit will decrease)
01 2.5
0 22.6
0 32.7
04 2.8
05 2.9
06 3.1
07 3.2
08 3.3
Current restriction
rate
Individual0 3
0 0 100% (Factory default)
When restriction option is set,
cooling and heating
performance may decrease
0 1 0.95
0 2 0.9
0 3 0.85
0 4 0.8
0 5 0.75
0 6 0.7
0 7 0.65
08 0.6
0 9 0.55
1 0 0.5
11 No r
estriction
Oil collection intervalMain 0 4
00 Factory default
01 Shorten the interval by 1/2
Temperature to
trigger defrost
operation
Main 0 5
00 Factory default
01
Apply setting when the product is
being
installed in humid area such as
near river or lak
e
Fan
speed correction
for outdoor unit
Individual0 6 0 0 Factory default
Silent mode for
night-time
Main 0 7
0 0 Disabled (Factory default)
Enable the silent mode for
night-time
(Itoperates automatically
depending on the temperrature.)
Howev
er, if the external contact
ineterface module(MIM-B14) is
used, entering the silent mode is
available with contact signal
0 1 LEVEL 1/Auto
0 2 LEVEL 2/Auto
0 3 LEVEL 3/Auto
0 4 LEVEL 1/External contact
0 5 LEVEL 2/External contact
0 6 LEVEL 3/External contact
Lon
g-piping condi-
tion setting (Setting is
unnecessary if
high-head condition
is set)
Main 0 9
0 0 Disabled (Factory default)
0 1 LEVEL 1
When equivalent length of farthest
indoor unit from the outdoor unit
is between 100~170m
0 2 LE
VEL 2
When equivalent length of
farthest
indoor unit from the outdoor unit
is over 170m
Energy saving setting Main 1 0
0 0 Disabled (Factory default)
01 Enabled
Energy saving mode triggers when
the room temperature reaches
desired temperature while
operating in heating mode
.