Key Options
Samsung Electronics 8-7
How to set the key function of the outdoor unit (cont.)
AM080ί2606XV666
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Emergency operation
for compressor
malfunction
Individual0 0
0 0 Disabled (Factory default)
E560 will occur when all the
compressors are set as
malfunction state.
01Set compressor 1 as malfunction state
0 2Set compressor 2 as m
alfunction state
Capacity correction
for cooling
Main 0 1
0 0 7-9 (Factory default)
T
argeted evaporation temperature
[?C] (When low temperature value
is set, discharged air temperature
of the indoor unit will decrease)
01 5-7
0 2 9-11
0 3 10-12
0 4 11-13
05 12-14
06 13-15
Capcity correction for
heating
Main 0 2
00 3.0 (Factory default)
T
argeted high pressure [MPa]
(When low pressure value is set,
discharged air temperature of the
indoor unit will decrease)
01 2.5
0 22.6
0 32.7
04 2.8
05 2.9
06 3.1
07 3.2
08 3.3
Current restriction
rate
Individual0 3
0 0 100% (Factory default)
When restriction option is set,
cooling and heating
performance may decrease
0 1 0.95
0 2 0.9
0 3 0.85
0 4 0.8
0 5 0.75
0 6 0.7
0 7 0.65
08 0.6
0 9 0.55
1 0 0.5
11 No r
estriction
Oil collection intervalMain 0 4
00 Factory default
01 Shorten the interval by 1/2
Temperature to
trigger defrost
operation
Main 0 5
00 Factory default
01
Apply setting when the product is
being
installed in humid area such as
near river or lak
e
Fan
speed correction
for outdoor unit
Individual0 6 0 0 Factory default
Silent mode for
night-time
Main 0 7
0 0 Disabled (Factory default)
Enable the silent mode for
night-time
(Itoperates automatically
depending on the temperrature.)
Howev
er, if the external contact
ineterface module(MIM-B14) is
used, entering the silent mode is
available with contact signal
0 1 LEVEL 1/Auto
0 2 LEVEL 2/Auto
0 3 LEVEL 3/Auto
0 4 LEVEL 1/External contact
0 5 LEVEL 2/External contact
0 6 LEVEL 3/External contact
Lon
g-piping condi-
tion setting (Setting is
unnecessary if
high-head condition
is set)
Main 0 9
0 0 Disabled (Factory default)
0 1 LEVEL 1
When equivalent length of farthest
indoor unit from the outdoor unit
is between 100~170m
0 2 LE
VEL 2
When equivalent length of
farthest
indoor unit from the outdoor unit
is over 170m
Energy saving setting Main 1 0
0 0 Disabled (Factory default)
01 Enabled
Energy saving mode triggers when
the room temperature reaches
desired temperature while
operating in heating mode
.