7-23 Cycle Component Function Explanation
1. Accumulator : Separating the incoming liquid refrigerant to the compressor in order to prevent liquid refrigerant.
2. Oil Separator : Separating the oil from the refrigerant discharged from the compressor, and the separ
ated oil is returned to the compressor.
3. Intercooler : Supercooled liquid refrigerant through the heat exchanger and makes the medium pressure gas refrigerant injected into the
compressor.
4. IPM Cooler : IPM (Intelligent Power Module) by
cooling to prevent overheating.
5. High/Low Pressure Sensor : Measure high/low Pressure of system.
6. High Pressure Switch : Suspend immediately for protection of system if high pressure of system exceeds setting value.
7. Outdoor EEV (Main EEV) : Adjust the in
coming refrigerant to the outdoor heat exchanger during heating operation.
8. EVI EEV : By adjusting the amount of refrigerant passing through the Subcooler to obtain the degree of supercooling and adjust the amount
of gas ref
rigerant entering to the compressor.
9. 4Way Valve : Change the direction of flow of the refrigerant to the cooling / heating operation.
10. ARV (Accumulator Oil Return Valve) : Remaining at the bottom of the Accumulator rec overed oil to the
compressor.
11. MainCooling Valve : In the main cooling operation, sending the high pressure refrigerant to indoor unit in heating mode.
12. Outdoor EEV Valve : In the main cooling operation, It's closed so that the Outdoor EEV Valve can control the amount of the ref
rigerant.
13. Hotgas Valve : Sending the high pressure gas to low pressure pipe in order to protect low pressure.
14. Hotgas Valve 2 : In the cooling operation, changing high pressure pipe to low pressure pipe.
15. EVI SOL V : This valve opens when using the va
por Injection.
16. E
VI BYPASS V : This valve opens in the sub cooling control. It's closed when using the vapor injection.
17. Discharge Temperature Sensor : Measure the temperature of the refrigerant discharged
from the compressor.
18. Suction Temp
erature Sensor : Meas
ure the temperature of the refrigerant to the compressor suction.
19. Cond. Out Temperature Sensor : Measure the temperature of the outdoor heat exchanger of the air conditioning operation.
2
0. EVI In/Out Temperature Sensor : Measure the temperature of the refrigerant inlet and outlet of the Subcooler.
21. Liquid Pipe Temperature Sensor : Measure the temperature of supercooling refrigerant in the outdoor unit o
f the air conditioning.
22. Comp. Top Temperature Sensor : Measure the temperature of compressor top cover.
23. Ambient Temperature Sensor : Measure the outdoor temperature.
24. Water
Temperature Sensor : Plate H
eat Exchanger internal temperature measurement
25. Control box temp. Sensor : Control box internal temperature measurement, thermal protection used for the control.
26. Receiver : Storing the refrigerant piping system, a stable liquid refrige
rant supply
27. Liquid Tube Valve : Refrigerant in the
outdoor unit side, the indoor unit during heating operation to rotate the valve operation.