Samsung Electronics 8-15
How to check the view mode using a tact switch (cont.)
㽞AM140/160/180/200/220/240/260/280/300KXV6666
K1 control KEY operation Display on segment
Press and hold
1 time
Auto trial operation “K” “K” “BLANK” “BLANK”
K1
(Number of press)
KEY operation
Display on segment
1 time Refrigerant charging in Heating mode “K” “1” “BLANK” “BLANK”
2 timesTrial operation in Heating mode “K” “2” “BLANK” “BLANK”
3 times Pump out in Heating mode (Outdoor unit address 1) “K” “3” “BLANK” “1”
4 times Pump out in Heating mode (Outdoor unit address 2) “K” “3” “BLANK” “2”
5 times Pump out in Heating mode (Outdoor unit address 3) “K” “3” “BLANK” “3”
6 times Pump out in Heating mode (Outdoor unit address 4) “K” “3” “BLANK” “4”
7 timesVacuumig (Outdoor unit address 1) “K” “4” “BLANK” “1”
8 timesVacuumig (Outdoor
unit address 2) “K” “4” “BLANK” “2”
9 timesVacuumig (Outdoor unit address 3) “K” “4” “BLANK “ “3”
10 timesVacuumig (Outdoor unit address 4) “K” “4” “BLANK” “4”
11 timesVacuuming (All outdoor units) “K” “4” “BLANK” “A”
12 timesEnd Key operation -
K2
(Number of press)
KEY operation
Display on segment
1 time Refrigerant charging in Cooling mode “K” “5” “BLANK” “BLANK”
2 times Trial operation in Cooling mode “K” “6” “BLANK” “BLANK”
3 times Pump down all units in Cooling mode “K” “7” “BLANK” “BLANK”
4 times
H/R: Checking the pipe connection
H/P: Automatic setting of
operation
mode
(Cooling/Heating) for trail operation
“K” “8” “BLANK” “BLANK”
5 timesChec
king the amount of refrigerant
“K” “9” X X
(Display of last two digits may differ
depending on the progress)
6 times Discharge mode of DC link voltage “K” “A” “BLANK” “BLANK”
7 times Forced defrost operation “K” “B” “BLANK” “BLANK”
8 times Forced oil collection “K” “C” “BLANK” “BLANK”
9 timesInverter compressor 1 check “K” “D” “BLANK” “BLANK”
10 times Inve
rter compressor 2 check “K” “E” “BLANK” “BLANK”
11 timesFan 1 check “K” “F” “BLANK” “BLANK”
12 timesFan 2
check “K” “G” “B
LANK” “BLANK”
13 timesEnd Key operation -
K3
(Number of press)
KEY operation
Display on segment
1 time Intialize (Reset) settingSame as initial state
ఐ During "Discharge mode of DC link voltage", voltage of INV1 and INV2 will be displayed alternately.
ఐ E v en when the outdoor unit power is off, it is dangerous when you come in contact with inverter PCB and fan PCB since they are
charged with high DC voltage.
ఐ Whe
n replacing/repairing the PCB, cut-off the power and wait until the DC voltage is discharged before replacing/ repairing them.
(Wait for more than 15 minutes to allow it to discharge naturally. )
ఐ W h en there
were error, '
Dich
arge mode of DC link voltage' may not have been effective Especialy if error E464 and E364 have been
occured, power element might be damaged by fire and therefore, do not use the 'Discharge mode of DC link voltage'.
K1 K2 K3 K4