8-16 Samsung Electronics
How to check the view mode using a tact switch (cont.)
㽞AM140/160/180/200/220/240/260/280/300KXV6666
K4
(Number of press)
KEY operation
Display on segment
Outdoor unit
model
SEG2, 3, 4
1 time Order frequency (Compressor 1) 1
AM160FXV6666
→
Off, 1, 6
2 timesOrder frequency (Compressor 2) 2
120 Hz
→
1, 2, 0
3 timesHigh pressure (MPa) 3
120 Hz
→
1, 2, 0
4 times Low pressure (MPa)4
1 52 MPa
→
1, 5, 2
5 times Discharge
temperature (Compressor 1) 5
0 43 MPa
→
0, 4, 3
6 times Discharge temperature (Compressor 2)6
87 °C
→
0, 8, 7
7 times IPM temperature (Compressor 1) 7
87 °C
→
0, 8, 7
8 times IPM temperature (Compressor 2)8
87 °C
→
0, 8, 7
9 timesCT sensor value (Compressor 1) 9
87 °C
→
0, 8, 7
10 times CT sensor value (Compre
ssor 2)A
2 A
→
0, 2, 0
11 times Suction temperature B
2 A
→
0, 2, 0
12 times COND OUT temperautre C
-42 °C
→
-, 4, 2
13 timesTemperature of liquid pipe D
-42 °C
→
-, 4, 2
14 times TOP temperature (Compressor 1) E
-42 °C
→
-, 4, 2
15 times TOP tempera
ture (Compressor 2)F
-42 °C
→
-, 4, 2
16 times Outdoor temperature G
-42 °C
→
-, 4, 2
17 times EVI inlet temperature H
-42 °C
→
-, 4, 2
18 times EVI outlet temperature I
-42 °C
→
-, 4, 2
19 timesMain EEV1 stepJ
-42 °C
→
-, 4, 2
20 timesMain EEV2 stepK
2000 steps
→
2, 0, 0
21 times EVI EEV stepL
2000 steps
→
2, 0, 0
22 times HR EEV stepM
300 steps
→
3, 0, 0
23 timesFan step (SSR or BLDC) N
300 steps
→
3, 0, 0
24 times Current frequency (Compressor 1) O
13 steps
→
0, 1, 3
25 times Current frequency (Compressor 2)P
120 Hz
→
1,2,0
26 times Su
ction 2 temperature (H/R) Q
120 Hz
→
1,2,0
27 timesMaster indoor unit address R
-42 °C
→
-, 4, 2
28 timesAddress of master indoor unit S
Master indoor unit not selected
→
BLANK, N, D
If indoor unit No 1 is selected as the master unit
→
0, 0, 1
K4
(Number of
press)
Press and hold
the K4 to enter
the setting
Displayed content
Display on segment
page1 page2
1 time Main version MAIN Version (ex 1412)
2 timesHub version HUB Version (ex 1412)
3 times Inverter 1 version INV1 Version (ex 1412)
4 times Inverter 2 version INV2 Version (ex 1412)
5 timesFan 1 version FAN1 Version (ex 1412)
6 timesFan 2 version FAN2 Version (ex 1412)
7 timesEEP version EEP Version (ex 1412)
8
times
Automatically assigned address of the
units
AUTO
SEG1 SEG2SEG3
Indoor unit: “A”
MCU: “C”
Indoor unit: “0”
MCU: “1”
Address
(ex: 07)
9 timesManually assigned address of the units MANU
SEG4 SEG5 SEG6
Indoor unit: “A” Indoor unit: “0”
Address
(ex: 15)
K1 K2 K3 K4