Product Specications
2-18 Samsung Electronics
TYPE
New Model Comparative Model
Model AM080FXVAGR AM100FXVAGR AM120FXVAGR RD080HRXG
6
RD100HRXG
6
RD120HRXG
6
Mode HR HR HR HR HR HR
Power Ø,V,Hz 3/AC380~415/50 3/AC380~415/50 3/AC380~415/50 3/AC380~415/50 3/AC380~415/50 3/AC380~415/50
Capacity
Horse Power HP 8 10 12 8 10 12
Capacity
kW 22.4 28.0 33.6 22.4 28.0 33.6
btu/h 76,400 95,500 114,600 76,400 95,500 114,600
Heating
kW 25.2 31.5 37.8 25.2 31.5 37.8
btu/h 86,000 107,500 129,000 86,000 107,500 129,000
Power
Power Input
(Nominal)
Cooling 1)
kW
5.00 6.80 8.40 - - -
Heating 2) 5.10 6.70 8.70 - - -
Current Input
(Nominal)
Cooling 1)
A
8.00 10.90 13.50 - - -
Heating 2) 8.20 10.70 14.00 - - -
Running
Current
Cooling A 8.00 10.90 13.50 8.80 13.00 20.00
Heating A 8.20 10.70 14.00 11.40 12.70 18.40
Max. A 18.00 21.10 25.00 18.40 21.50 28.40
Power
Consumption
Cooling kW 5.00 6.80 8.40 5.20 7.04 9.20
Heating kW 5.10 6.70 8.70 5.46 6.89 8.50
MCA / MFA A 22.5 / 30 29.9 / 40 31.3 / 40 - - -
COP
Nominal Cooling - 4.48 4.12 4.00 - - -
Nominal Heating - 4.94 4.70 4.34 - - -
ESEER (HP) 7.85 7.25 7.03 - - -
Compressor
Model - DS-GB052FA**** DS-GB066FA**** DS-GB066FA****
ZPJ61KCE-TFD
ZPI61KCE-TFD
ZPJ61KCE-TFD
ZPI61KCE-TFD
ZPJ83KCE-TFD
ZPI83KCE-TFD
Type INV x1 INV x1 INV x1 DVI x1 + FVl x1 DVI x1 + FVl x1 DVI x1 + FVl x1
Output kW 4.70 5.80 5.80 4.36 + 4.36 4.36 + 4.36 5.87 + 5.87
Lubricant
Type - FVC68D
FVC68D FVC68D 3MAF POE 3MAF POE 3MAF POE
Charging cc 3,900 3,900 3,900 4,370 4,370 4,370
Refrigerant
Type - R410A R410A R410A R410A R410A R410A
Factory Charging kg 5.5 5.2 5.5 5.0 5.0 5.0
FA N
Type - Propeller + BLDC Propeller + BLDC Propeller + BLDC Propeller + BLDC Propeller + BLDC Propeller + BLDC
Motor Output W 400 400 400 630 630 630
Airflow rate
᎑ ΞΚΟ
173 173 210 173 173 210
Pipe
Piping
Connections
Liquid
Ø,mm 9.52 9.52 12.70
9.52 9.52 12.70
Ø,inch 3/8" 3/8" 1/2"
Gas
Ø,mm 19.05 22.22 28.58
19.05 22.22 25.40
Ø,inch 3/4" 7/8" 1 1/8"
Dis. Gas
Ø,mm 15.88 19.05 19.05
15.88 19.05 22.22
Ø,inch 5/8" 3/4" 3.4"
Installation
Limitation
Max.Length m 200(220) 200(220) 200(220) 200 200 200
Max.Height m 110(40) 110(40) 110(40) 50(40) 50(40) 50(40)
Cable
Main Power(Below/about20m) mm2 4.0 4.0 4.0 1.5 2.5 4.0
Communication mm2 VCTF 0.75~1.5(2P) VCTF 0.75~1.5(2P) VCTF 0.75~1.5(2P) VCTF 0.75~1.5(2P) VCTF 0.75~1.5(2P) VCTF 0.75~1.5(2P)
Set
Dimension
Net Weight
DVM S HP
kg
190.0 190.0 190.0
243 243 243
DVM S HR 195.0 195.0 195.0
Shipping
Weight
DVM S HP
kg
206.0 206.0 206.0
259 259 259
DVM S HR 211.0 211.0 211.0
Net Dimension(WxHxD) mm 880x1,695x765 880x1,695x765 880x1,695x765 880x1695x765 880x1695x765 880x1695x765
Gross Dimension(WxHxD) mm 948x1,657x832 948x1,657x832 948x1,657x832 948x1912x832 948x1912x832 948x1912x832
Operating
Temp Range
Cooling
DVM S HP
ఁ
-5.0~48.0 -5.0~48.0 -5.0~48.0
-5.0 ~ 48.0 -5.0 ~ 48.0 -5.0 ~ 48.0
DVM S HR -15.0~48.0 -15.0~48.0 -15.0~48.0
Heating -20.0~24.0 -20.0~24.0 -20.0~24.0 -20.0 ~ 24.0 -20.0 ~ 24.0 -20 .0~ 24.0
Outdoor Unit (cont.)
1. Proper form capacity standard of air conditioning
- Cooling capacity : It is figures that appear in indoor 27˚C DB/19°C WB, outdoor 35˚C DB, length 7.5m of piping, fall 0m standard.
- Heating capacity : It is figures that appear in indoor 20˚C DB, outdoor 7˚C DB, length 7.5m of piping, fall 0m standard.
2. If proper form heating capacity is outdoor temperature 7˚C standard and outdoor temperature goes down by below zero, heating capacity can drop according to temperature condition.
3. Need special load calculation in case of use by main heating in the winter, and please buy product for low temperature that heating effect excels at low temperature.
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m).
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m.