Samsung Electronics 8-11
How to set the key function of the outdoor unit (cont.)
AM140/160/180/200/220/240/260/280/300KXV6666
Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Long-pipng
condition
setting
(Setting
is unnecessary
if high-head
condition is set)
Main 0 9
0 0 Disabled (Factory default)
0 1 LEVEL 1
When equivalent length of
farthest indoor unit from
the outdoor unit is between
100~170m
0 2 LEVEL 2
When equivalent length of
farthest in
door unit from the
outdoor unit is over 170m
Energy control
Operaton
Individual1 0
00 Basic (Factory default) Energy control option
of designated operation
sequence.
Operating in energy
saving mode, capacity
might decrease c
ompared
to normal operation mode.
01 Energy saving
0 2 Power
Rotation defrost
(HR only)
Main 1 1
0 0 Disabled (Factory default)
01 Enabled
When enabled, continuous
heating operation is possible
but heating performance
will decrease during rotation
defrost ope
ration.
Expand
operational
temperature
range for cooling
operation
(HR only)
Individual1 2
0 0 Disabled (Factory default)
01 Enabled
When enabled, continuous
cooling operation is possible
even in low temperature
condition up to -15°C, but
noise o
f the MCU will increase.
Channel address Main 1 3
AU
Automatic setting
(Factory default)
Address for classifying the
product from upper level
controller. (DMS, S-NET 3, etc )
0 ~ 15
Manual setting for channel
0~15
Snow
accumulation
prevention
control
Main 1 4
00 Enabled (Factory default)
During snow accmulation , the
fan may spin even when the
unit is not in operation.
0 1 Disabled
Unused option Main 1500 Unused option Unused option by this model.
Unused option Main 1600 Unused option Unused option by this model.
Speed operation Main 1 7
0 0 Disabled (Factory default)
Enabling this s
etting will
command the air conditioner
to cool/ heat faster at initial
start-up.
However, this function will
not work when High-head
condition setting or Longpiping
condition setting is
enabled.
01 Enabled
Max capacity
restriction
Main 1 8
00 Enabled (Fac
tory default)
Restrict excessive capacity
increase when operating
indoor units with small
capacity.
0 1 Disabled
Gasleak
Pumpdown
Main 1 9
0 0 Disabled (Factory default)
If the gas leak occurred it
should be entered in the
pumpdown operation.
01 Enabled