2-42 Samsung Electronics
Outdoor Unit (cont.)
1. Proper form capacity standard of air conditioning
- Cooling capacity : It is figures that appear in indoor 27˚C DB/19°C WB, outdoor 35˚C DB, length 7.5m of piping, fall 0m standard.
- Heating capacity : It is figures that appear in indoor 20˚C DB, outdoor 7˚C DB, length 7.5m of piping, fall 0m standard.
2. If proper form heating capacity is outdoor temperature 7˚C standard and outdoor temperature goes down by below zero, heating capacity can drop according to temperature condition.
3. Need special load calculation in case of use by main heating in the winter, and please buy product for low temperature that heating effect excels at low temperature.
4. Maximum length between outdoor and indoor units allows up to 200m (Equivalent length 220m).
5. If the indoor unit is below, height length allows up to 110m (If over 50m, decide whether to install the PDM kit). If the outdoor unit is below, allowable height length is 40m.
TYPE
New Model
Model
AM240KXVANH/TL AM260KXVANH/TL AM280KXVANH/TL AM300KXVANH/TL AM220KXVJNH/ID AM240KXVJNH/ID
Mode
HP HP HP HP HP HP
Power
Φ, V,
Hz
3/AC380-415/50-60 3/AC380-415/50-60 3/AC380-415/50-60 3/AC380-415/50-60 3/AC380-415/50-60 3/AC380-415/50-60
Capacity
Horse Power HP
24 26 28 30 22 24
Cooling kW
67.2 72.8 78.6 84.0 61.6 67.2
Heating kW
75.6 81.9 88.2 94.5 69.3 75.6
Power
Power input
(Nominal)
Cooling 1)
kW
17.10 18.91 20.68 22.70 15.50 17.10
Heating 2)
17.42 18.00 20.18 20.59 15.80 17.42
Current
Input
(Nominal)
Cooling 1)
A
27.40 30.30 33.20 36.40 24.80 27.40
Heating 2)
27.90 28.90 32.40 33.00 25.30 27.90
Running
Current
Cooling A
27.40 30.30 33.20 36.40 24.80 27.40
Heating A
27.90 28.90 32.40 33.00 25.30 27.90
Max A
55.0 60.0 67.0 73.0 57.1 63.3
Power
Consump-
tion
Cooling kW
17.10 18.91 20.68 22.70 15.50 17.10
Heating kW
17.42 18.00 20.18 20.59 15.80 17.42
MCA/MFA A
55.0 / 75 60.0 / 75 67.0 / 75 73.0 / 90 57.1 / 75 63.3 / 75
COP
Nominal Cooling -
3.930 3.850 3.800 3.700 3.970 3.930
Nominal Heating -
4.340 4.550 4.370 4.590 4.390 4.340
ESEER (HP) -
------
Compressor
Model -
DS-GB066FA* DS-GB066FA* DS-GB070FA* DS4G*5080F* DS-GB066FA* DS-GB066FA*
Type
INV x 2EA INV x 2EA INV x 2EA INV x 2EA INV x 2EA INV x 2EA
Output kW
6.39 x 2 6.39 x 2 6.76 x 2 7.81 x 2 6.39 x 2 6.39 x 2
Lubricant
Type -
PVE PVE PVE PVE PVE PVE
Charging cc
1100 x 2 1100 x 2 1100 x 2 1400 x 2 1100 x 2 1100 x 2
Refrigerant
Type -
R410A R410A R410A R410A R410A R410A
Factory Charging kg
12.5 12.5 14.0 14.0 10.0 10.0
Fan
Type -
Propeller + BLDC Propeller + BLDC Propeller + BLDC Propeller + BLDC Propeller + BLDC Propeller + BLDC
Motor Output W
620 x 2 620 x 2 620 x 2 620 x 2 620 x 2 620 x 2
Airow rate
᎑
ΞΚΟ
340 340 340 340 340 340
Piping
Connections
Liquid pipe
Φ, mm
15.88 19.05 19.05 19.05 15.88 15.88
Φ, inch
5/8" 3/4" 3/4" 3/4" 5/8" 5/8"
Gas pipe
Φ, mm
34.92 34.92 34.92 34.92 28.58 34.92
Φ, inch
1+3/8" 1+3/8" 1+3/8" 1+3/8" 1+1/8" 1+3/8"
High pressure gas pipe
Φ, mm
------
Φ, inch
------
Installation
Limitation
Max. Length m
220 220 220 220 220 220
Max. Height m
50(110)/40 50(110)/40 50(110)/40 50(110)/40 50(110)/40 50(110)/40
Cable
Main Power(Below 20m) mm2
------
Communication mm2
------
Set
Dimension
Net weight kg
333 333 342 350 330.5 330.5
Gross weight kg
355 355 364 372 352.5 352.5
Net dimension (WxHxD) mm
1295x1795x765 1295x1795x765 1295x1795x765 1295x1795x765 1295x1795x765 1295x1795x765
Gross dimension (WxHxD) mm 1363x1987x832 1363x1987x832 1363x1987x832 1363x1987x832 1363x1987x832 1363x1987x832
Operating
Temp. Range
Cooling
ఁ
-5 ~ 48 -5 ~ 48 -5 ~ 48 -5 ~ 48 -5 ~ 54 -5 ~ 54
Heating
ఁ
-25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24 -25 ~ 24