Optional item Input unit SEG1 SEG2 SEG3 SEG4 Function of the option Remarks
Emergency
operation for
compressor
malfunction
Individual 0 0
0 0 Disabled (Factory default)
E560 will occur when all
the compressors are set as
malfunction state.
01
Set compressor 1 as
malfunction state
02
Set compressor 2 as
malfunction state
Cooling capacity
correction
Main 0 1
00
7-9 (Factory default in case
of A type PBA)
Targeted evaporation
ϩʪΧʪθɇϩЇθʪࣈঌAࣉ࢏
(When low temperature
value is set, discharged air
temperature of the indoor
unit will decrease)
01
5-7 (Factory default in case
of B type PBA)
02 9-11
03 10-12
0 4 11-13
05 12-14
06 13-15
Capacity
correction for
heating
Main 0 2
0 0 3.0 (Factory default)
Targeted high pressure
[MPa].
(When low pressure value
is set, discharged air
temperature of the indoor
unit will decrease)
01 2.5
02 2.6
03 2.7
04 2.8
05 2.9
06 3.1
07 3.2
08 3.3
Current
restriction rate
Individual 0 3
0 0 100% (Factory default)
When restriction option is
set, cooling and heating
performance may decrease.
01 95 %
02 90 %
03 85 %
04 80 %
05 75 %
06 70 %
07 65 %
08 60 %
0 9 55 %
10 50 %
1 1 No restriction
Oil collection
interval
Main 0 4
0 0 Factory default
0 1 Shorten the interval by 1/2
Temperature to
trigger defrost
operation
Main 0 5
0 0 Factory default
01
Apply setting when the
product is being installed
in humid area such as near
river or lake
Fan speed
correction for
outdoor unit
Individual 0 6
0 0 Factory default
0 1 Increase fan speed
Increase the outdoor unit's
fan speed to maximum
value
Setting outdoor unit option switch and key function