3. To prevent any gas from leaking out, remove all
burrs at the cut edge of the pipe, using a reamer.
4. Slide a flare nut on to the pipe and modify the
flare.
Outer Diameter(D) Depth(A)
19.52 mm (3/8") 1.8 mm
15.88 mm (5/8") 2.2 mm
5. Check that the flaring is correct, referring to the
illustrations below for examples of incorrect
flaring.
6. Align the pipes and tighten the flare nuts first
manually and then with a wrench, applying the
following torque.
Outer Diameter(D) Torque (kgf•cm)
19.52 mm (3/8") 300
15.88 mm (5/8") 750
7. For further details on how to connect up to the
outdoor unit and purge the circuit.
4-29
Samsung Electronics
Installation
Caution :
In case of welding the pipe, you must weld with nitrogen gas
blowing.
Duct-ADH1800E-2-2 6/27/00 10:37 AM Page 4-29