EasyManua.ls Logo

Samsung DH32ZA1 - Increasing Fan Speed

Samsung DH32ZA1
133 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Samsung Electronics
4-4-21. Increasing Fan Speed
If external static pressure is too great(due to long extension of ducts, for example), the air flow volume may drop too
low at each air outlet. This problem can be solved by increasing the fan speed using the following procedure.
1. Remove the screw on the electrical component box and
remove the cover plate.
2. Adjust the DIP switch(SW2) on the main PCB to the “OFF”
position.
3. Re-install the cover plate and join the removed screw.
How to Read Diagram
1. The vertical axis is the external static pressure(mmAq) while the horizontal axis represents the AIR
FLOW(m
3
/min).
2. The characteristic curves for ‘HH’, ‘H’, ‘Med’, and ‘Low’ fan speed controller are shown.
3. The nameplate values are shown based on the ‘H’ air flow.
4. In case of model ADH2400E/DH24ZA1(A2), the air flow is 17.4(m
3
/min), while the external static
pressure is 4mmAq at ‘H’ position.
5. If external static pressure is too great, the air flow volume may drop too low as explained above.
Note : HH : DIP Switch OFF position(High speed) H : At shipment(Normal speed)
4-36
Installation
ADH2400E, DH24ZA1(A2)
Air Flow (m
3
/min)
mmAq
ADH3200E, DH32ZA1(A2)
Air Flow (m
3
/min)
mmAq
ADH1800E, DH18ZA1(A2)
Air Flow (m
3
/min)
mmAq
Switch No.
5
Switch Position
ON
OFF
Function
Normal speed
High speed
Duct-ADH1800E-2-2 6/27/00 10:37 AM Page 4-36