13
ENGLISH
Installation example 2) AHU KIT + contact signal for AHU fan ON
1(L) 2(N)
F1 F2 F3 F4 V1 V2 1 243CBA
mA
-+ Vd Vd
Contact signal for fan ON
AHU MOTOR
AHU
controller
AHU MOTOR
POWER SOURE
❋ AHU KIT outputs only contact signals for FAN output.
Use the FAN output signal from the AHU controller to control the AHU FAN motor.
(Do not connect the FAN oupt signal directly to driving part.)
Installation example 3) Setting a room temperature sensor for installing multiple AHU KITs
ABC
ABC
ABC
ABC
F3 F4
F3 F4
F3 F4
F3 F4
F3 F4
Wired remote
controller
SLAVE AHU Kit 3
MASTER AHU Kit
SLAVE AHU Kit 2
SLAVE AHU Kit 1
Room
temperature
sensor PT1000
• For common AHU with multiple AHU KITS, sharing with 1 room temperature sensor is possible. The room
temperature sensor sharing uses the communication of wired remote controller, so Wired remote controller
should be installed. mA temperature sensor is the same as well. (Refer to SEG 24 of installation option 05 series
on page 26.)
• If one room temperature sensor is used for multiple AHU kits, MCM-D201N should only be used.
CAUTION