16
Installing an AHU KIT
Installing IN/OUT sensor
1. Attach the EVA IN sensor after the distributor and on the lowest temperature pipe of a heat exchanger.
2. Install the EVA OUT sensor 200mm after the header of AHU heat exchanger as shown in the picture.
3. Insulate the EVA IN and OUT sensor so that it is not aected by wind.
4. Install the ROOM temperature sensor on the RA(Return Air) path of AHU.
Selecting the location of EVA_IN/OUT sensor
200

2 EVA OUT sensor
1 EVA IN sensor
Header
Distributor
Cool mode
Heat mode
Refrigerant ow
Example of ROOM temperature sensor installation
Location of room temperature sensor
Return air
Outdoor air
Exhaust air Supply air
In principle, the sensor holder of EVA IN/OUT sensor should be welded at the designated place and then the EVA
IN/OUT sensor should be xed with a clip.
EVA IN/OUT sensor should be installed at the place where temperature of the heat exchanger air inlet or outlet
can be measured accurately.
NOTE