Installing an AHU KIT
Example of IN/OUT sensor installation 2
1. Chcek the sensor and sensor holder you will attach.
Type
Diameter of a
sensor (mm)
Diameter of a sensor
holder (mm)
IN sensor(Blue) ø 6 ø 6.8
OUT sensor(Red) ø 7 ø 7.8
NOTE
Insulator
Aluminum tape Rubber tape
IN/OUT
sensor
Cable tie
2. Attach the sensor closely to the pipe.
Attaching a sensor
Attach the sensor at the place where temperature
detection is easily available. (Refer to p.16)
Attach the sensor as closely as possible on the surface of
the pipe.
Do not use a sensor holder.
NOTE
Sensor
Pipe
3. After attaching the sensor on the pipe, cover it with aluminum
tape.
Aluminum tape
IN/OUT sensor
4. Cover the sensor with rubber tape.
Rubber tape
IN/OUT sensor
5. Fix the sensor with cable ties.
Cable tie
6. Attach the insulator around the attached sensor.