18
Installing an AHU KIT
Example of IN/OUT sensor installation 2
1. Chcek the sensor and sensor holder you will attach.
Type
Diameter of a
sensor (mm)
Diameter of a sensor
holder (mm)
IN sensor(Blue) ø 6 ø 6.8
OUT sensor(Red) ø 7 ø 7.8
NOTE
Insulator
Aluminum tape Rubber tape
IN/OUT
sensor
Cable tie
2. Attach the sensor closely to the pipe.
Attaching a sensor
• Attach the sensor at the place where temperature
detection is easily available. (Refer to p.16)
• Attach the sensor as closely as possible on the surface of
the pipe.
• Do not use a sensor holder.
NOTE
Sensor
Pipe
3. After attaching the sensor on the pipe, cover it with aluminum
tape.
Aluminum tape
IN/OUT sensor
4. Cover the sensor with rubber tape.
Rubber tape
IN/OUT sensor
5. Fix the sensor with cable ties.
Cable tie
6. Attach the insulator around the attached sensor.