23
ENGLISH
Setting the installation option of an AHU KIT (suitable for the condition of each installation location)
1. Check whether power is supplied or not.
- When the AHU KIT is not plugged in, there should be additional power supply.
2. The reception part of a remote controller is built in the AHU KIT PBA.
3. Set the installation option of an AHU KIT according to installation conditions.
- The default setting of an AHU KIT installation option is “020010-100000-200000-300000”.
4. Set the AHU KIT option with a remote controller.
■ 02 series installation option
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
02-
External room
temperature sensor/
Minimizing fan operation
when thermostat is o
Central control -
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1---
EEV Step when
heating stops
-
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2 External control
External control
output
- Buzzer -
SEG19 SEG20 SE21 SEG22 SEG23 SEG24
3-
Compensation of
heating setting
Oil return/EEV step
of stopped defrost
mode
--
f SEG5 central control option is basically set as 1 (Use), so you don’t need to set the central control option additionally.
When you exclude the indoor unit control from central control, change the setting as 0(Disuse).
f When you set the value other than the SEG setting values, it will be set as "0".
Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2 SEG3 SEG4
(*1)
SEG5 SEG6
Explanation
PAG E
MODE Use of robot cleaning
Use of external room temperature sensor/Minimizing
fan operation when thermostat is o
Use of central control FAN RPM compensation
Remote
Controller
Display
Indication and
Details
Indication Details Indication Details Indication Details
Indication
Details Indication Details
0
2
0 Disuse
Use of
External room
temperature
sensor
Minimizing fan
operation when
thermostat is o
0 Disuse
0
Disuse Disuse
1
Use Disuse
1Use
2
Disuse Heating Use
3
Use Heating Use
4
Disuse Cooling Use
5
Use Cooling Use
6
Disuse All Use
7
Use All Use