25
ENGLISH
(*1)
Minimizing fan operation when thermostat is o
- Fan operates for 20 seconds at an interval of 5 minutes in heating mode.
- Fan stops when thermostat is o in cooling mode.
- Make sure to connect the wired remote controller or the external room temperature sensor if you use the function of
external room temperature sensor or minimizing fan operation. (In order to implement the functions the option of
using temperature sensor inside the wired remote controller must be set. Refer to the installation manual of the wired
remote controller.
■ 05 series installation option
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
05
Use of Auto Change
Over for HR only in
Auto mode
(When setting SEG3)
Standard heating temp.
Oset
(When setting SEG3)
Standard cooling
temp. Oset
(When setting SEG3)
Standard for mode
change Heating →
Cooling
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1
(When setting SEG3)
Standard for mode
change Cooling →
Heating
(When setting SEG3)
Time required for
mode change
Compensation option
for Long pipe or height
dierence between
indoor units
--
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2- - -
Temperature control
by using simple BMS
-
SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
3 HP setting Fan Feedback Defrost signal
Skip the prevention
of cold air
Sensor
■ 05 series installation option(Detailed)
Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation
PAGE MODE
Use of Auto Change Over
for HR only in Auto mode
(When setting SEG3)
Standard heating temp. Oset
(When setting SEG3)
Standard cooling temp. Oset
(When setting SEG3)
Standard for mode change Heating
→
Cooling
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
05
0
Follow
product
options
00000 1
1
Use Auto
Change Over
for HR only
1 0.5 1 0.5 1 1.5
21212 2
3 1.5 3 1.5 3 2.5
42424 3
5 2.5 5 2.5 5 3.5
63636 4
7 3.5 7 3.5 7 4.5