26
Setting an address and installation option of AHU KIT
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation PAGE
(When setting SEG3)
Standard for mode change
Cooling
→
Heating mode
(When setting SEG3)
Time required for mode
change
Compensation option for Long
pipe or height diference between
indoor units
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details
1
0 1 0 5 min. 0 Use default value
1 1.5 1 7 min.
1
1) Height dierence
1)
is
more than 30m or
2) Distance
2)
is longer
than 110m
2 2 2 9 min.
3 2.5 3 11 min.
4 3 4 13 min.
2
1) Height dierence
1)
is
15~30m or
2) Distance
2)
is
50~110m
5 3.5 5 15 min.
6 4 6 20 min.
7 4.5 7 30 min.
Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
Explanation 2
-- -
Simple BMS temperature
control
-
Indication Details
0
Room
temperature
1
Discharge
temperature
Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
Explanation PAGE HP setting Fan Feedback Defrost signal Skip the prevention of cold air Sensor
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
0
Default
(10 HP)
0 Disuse 0 Disuse 0 Disuse 0
Sharing the room and discharge
temperature value of a master
indoor unit
1 10 HP 1 Use 1 Use 1 Use 1
Master indoor unit
- Room temperature : PT1000
- Discharge temperature :
4~20 mA
2 20 HP 2
Master indoor unit
- Room temperature : 4~20 mA
- Discharge temperature :
PT1000
3 30 HP
3
Master indoor unit
- Room temperature : a wired
remote controller’s sensor
- Discharge temperature :
4~20 mA
4 40 HP
1) Height dierence : The dierence of the height between the corresponding indoor uint and the indoor unit installed at the lowest place.
For example, When the indoor unit is installed 40m(131.23ft) higher than the indoor unit installed at the lowest place, select the option "1".
2) Distance : The dierence between the pipe length of the indoor unit istalled at the farthest place from an outdoor unit and the pipe length of the corresponding indoor unit from an outdoor
unit. For example, when the farthest pipe length is 100m(328ft) and the corresponding indoor unit is 40m(131.23ft) away from an outdoor unit, select the option "2". (100m(328ft) -
40m(131.23ft) = 60m(196.85ft))
3) Regardless of the AHU KIT HP setting, one indoor unit will be recognized. Therefore, be careful when setting the number of the indoor unit installation with an outdoor unit.
3)