5. For checking EEV service, please attach a label sticker.
f Attach one label to upper middle part of ASS'Y EEV valve body and attach the same color of a lable sticker to valve wire
housing.
6. Connect the EEV termial block to exact places on PCB according to set HP.
f When the set HP of AHU KIT is set as 40 HP: Connect EEV-1, EEV-2, EEV-3 and EEV-4
f When the set HP of AHU KIT is set as 30 HP: Connect EEV-1, EEV-2, and EEV-3.
f When the set HP of AHU KIT is set as 20 HP: Connect EEV-1 and EEV-2
EEV-1 EEV-3EEV-2
EEV-4
Wire saddle
EEV connector connection should be xed to the wire saddle as shown in the image.
New AHU KIT (ACM-D201N) has a dierent way to set the number of the indoor unit installation from the
previous AHU KIT (ACM-D201) and an outdoor unit.
Be careful when setting the number of the indoor unit installation with an outdoor unit.
When setting AHU KIT HP, refer to the SEG 20 of Installation option 05 series on page 26.
Regardless of the AHU KIT HP setting, one indoor unit will be recognized.