5. For checking EEV service, please attach a label sticker.
f Attach one label to upper middle part of ASS'Y EEV valve body and attach the same color of a lable sticker to valve wire
housing.
6. Connect the EEV termial block to exact places on PCB according to set HP.
f When the set HP of AHU KIT is set as 40 HP: Connect EEV-1, EEV-2, EEV-3 and EEV-4
f When the set HP of AHU KIT is set as 30 HP: Connect EEV-1, EEV-2, and EEV-3.
f When the set HP of AHU KIT is set as 20 HP: Connect EEV-1 and EEV-2
EEV-1 EEV-3EEV-2
EEV-4
Wire saddle
❋ EEV connector connection should be xed to the wire saddle as shown in the image.
• New AHU KIT (ACM-D201N) has a dierent way to set the number of the indoor unit installation from the
previous AHU KIT (ACM-D201) and an outdoor unit.
• Be careful when setting the number of the indoor unit installation with an outdoor unit.
• When setting AHU KIT HP, refer to the SEG 20 of Installation option 05 series on page 26.
• Regardless of the AHU KIT HP setting, one indoor unit will be recognized.
CAUTION