3
1.4 Product specification and performance
General specification
50
(176-276)VAC
31A max.
46Hz~54Hz
>0.98(Full load)
240VDC
24A max.
220VAC
27A
50
(176-276)VAC
31A max.
46Hz~54Hz
>0.98(Full load)
240VDC
24A max.
220VAC
27A
1%
0.7 lag
50
(176-276)VAC
50A max.
46Hz~54Hz
>0.98(Full load)
240VDC
40A max.
220VAC
45A
50
(176-276)VAC
50A max.
46Hz~54Hz
>0.98(Full load)
240VDC
40A max.
220VAC
45A
Voltage
Current
Frequency
Power Factor
Voltage
Current
Voltege
Current
Voltage regulation
Power Factor
Distortion
Overload capacity
Input
Battery
Output
Model
Power Rating
Frequency (Hz)
1. Brief introduction
6kVA/4.2kW 6kVA/4.2kW 10kVA/7kW 10kVA/7kW
C6K(e) C6KS(e) C10K(e) C10KS(e)
105%-130% load transfers to bypass mode after 10 minutes
>130% load transfers to bypass mode after 1 second and shutdown
the output after 1 minute
±
Synchronized 46-54Hz in Line mode(AC mode)
0.1% of normal frequency in Battery mode
±
Frequency tolerance
THD<2% Full load (Linear load)
Current crest ratio 3:1 maximum
Operating environment
<95%
<1000m
Temperature
0 -40
Humidity
Altitude Storage temperature
0 -40
Note: If the UPS is installed or uesd in a place where the altitude is above than 1000m, the
output power must be derated in use, please refer to the following:
Altitude (M)
Derating power
1000
1500 2000 2500 3000 3500 4000 4500
100%
95%
91%
86%
82%
5000
78% 74%
70%
67%