EasyManua.ls Logo

SANUPS A11H - Setup Menu List

Default Icon
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Settings
34
§
§
1
1
2
2
.
.
2
2
S
S
e
e
t
t
u
u
p
p
M
M
e
e
n
n
u
u
L
L
i
i
s
s
t
t
User Settings Guide
No.
Ref. page
Item
Menu Menu LED Setting
Setting
LED
Default
Setting
Current
Setting
Remarks
- ●○○○
- ○●○○
- ●●○○
Do not use these settings.
1 4 3.1 Output voltage
○
●○○○
120 V ○○●○
*
120 V
1% ●○○○
±1%
3% ○●○○
±3%
2 5 3.2
Frequency sync
range (RESTART)
○
○●○○
5% ●●○○
*
±5%
Output frequency variation range (%)
50Hz ●○○○
50Hz
3 6 3.3
Output frequency
(RESTART)
○
●●○○
60Hz ○●○○
*
60Hz
Standalone ●○○○
Set when using UPS remote ON/OFF or Standard OS UPS
Services
Workstation ○●○○
*
Set when using a power management software, LAN card or
UPS remote ON and One-touch system shutdown.
Serial Login ●●○○
Shutdown by serial login.
4 7 3.4 PC interface
○
○○●○
- ○○●○
Do not use this setting.
9600 ●○○○
*
9600 bps.
4800 ○●○○
4800 bps.
5 8 3.5 Serial baud rate
○
●○●○
2400 ●●○○
2400 bps.
Set the serial baud rate when a
workstation, PC, or optional LAN
card is connected.
Auto ●○○○
*
Auto restart
OFF ○●○○
The UPS stays off.
30% ●●○○
Auto restart when battery
charge reaches 30%.
50% ○○●○
Auto restart when battery
charge reaches 50%.
6 9 3.6
UPS operation upon
power recovery
○
○●●○
80% ●○●○
Auto restart when battery
charge reaches 80%.
Specify when to restart the UPS
after a power outage and
shutdown of the UPS due to final
discharge of the batteries.
All patterns ●○○○
*
All sounds
Pattern 1 ○●○○
Emit sounds on serious failure and battery trouble.
Pattern 2 ●●○○
Emit alarm and key click sounds.
7 10 3.7 Buzzer sound
○
●●●○
OFF ○○●○
Emit key click sounds only.
1 second ●○○○
*
Turn the UPS off when
pressed for 1 second.
3 seconds ○●○○
Turn the UPS off when
pressed for 3 second.
8 11 3.8 Shutdown operation
○
○○○●
Special
operation
●●○○
Turn the UPS off on
special operation.
Set the operation for switch to stop
the UPS power supply.
Auto return ●○○○
Auto recovery when a
certain period of time has
elapsed.
9 12 3.9
Overload recovery
operation
○
●○○●
Bypass ○●○○
*
Fixed as bypass power
supply on overload.
Set the UPS operation after
switching to the bypass power
supply because of overload.
OFF ●○○○
*
The UPS stays off.
10 13 3.10
UPS operation at
OFF
(RESTART)
○
○●○●
Bypass ○●○○
Bypass power supply
Specify the UPS power supply
conditions when is off.
Battery voltage ●○○○
*
When low battery voltage
level is detected.
2 minutes ○●○○
When remaining battery
duration is 2 minutes.
11 14 3.11
Low battery voltage
warning timing
○
●●○●
3 minutes ●●○○
When remaining battery
duration is 3 minutes.
Set the timing of emitting the low
battery voltage warning alarm
(beep, Red BATT. LOW lit).
12
min.
10
min.
●○○○
20
min
.
18
min.
○●○○
See
remarks
Set the UPS backup time on power outage.
-
○●●○
-
●●●○
-
○○○●
-
○●●○
-
●●●○
-
○○○●
-
●○○●
-
○●○●
12 15 3.12 Battery backup time
○
○○●●
-
●●○●
Do not use these settings.
Default setting varies depending
on UPS Model.
Default setting of each Model is as
follows.
A11H202U011TW : 12 minutes
A11H202U111TW : 20 minutes
A11H302U011TW : 10 minutes
A11H302U111TW : 18 minutes
5 years ●○○○
*
5 years lifetime type
10 years ○●○○
10 years lifetime type
13 16 3.13 Battery type
○
●○●●
3 years ●●○○
3 years lifetime type
Set the battery type. Set this when
you replace the battery or connect an
external battery.
180 days ●○○○
*
Test batteries every 180 days.
90 days ○●○○
Test batteries every 90 days.
30 days ●●○○
Test batteries every 30 days.
14 17 3.14 Battery test schedule
○
○●●●
None ○○●○
No battery check.
Set the interval (number of days)
for the automatic battery check.
The check is carried out
automatically when the specified
number of days has elapsed.
Do not reset ●○○○
*
Do not reset.
15 18 3.15
Reset battery
information
○
●●●●
Reset ○●○○
Reset the battery information when you replace the battery.
●: indicates that LED is blinking.
○: indicates that LED is off.

Table of Contents