1-10. Airfl ow Distance Chart
4-Way Air Discharge Semi-Concealed Type
If an ultra long-life fi lter or high performance fi lter (65% by colorimetric method) is installed, the vertical air fl ow
distance for heating and cooling will be approximately 0.2 m less than the values shown in the graph below.
If a high performance fi lter (90% by colorimetric method) or electronic fi lter is installed, the vertical air fl ow
distance for heating and cooling will be approximately 0.5 m less than the values shown in the graph below.
Vertical air flow distance (m)Vertical air flow distance (m)Vertical air flow distance (m)Vertical air flow distance (m)
Horizontal air flow distance (m)
Heating : Distribution of wind velocity
Heating : Distribution of temperature
0
54321012345
1
2
3
0
1
2
3
Horizontal air flow distance (m)
0
54321012345
1
2
3
0
1
2
3
(Strong wind : Discharge angle approx.65 ) (Room temperature approx.20 )
(Strong wind : Discharge angle approx.65 ) (Room temperature approx.20 )
1.5m/s
1.0m/s
0.5m/s
0.3m/s
33
27
24
30
Horizontal air flow distance (m)
Cooling : Distribution of wind velocity
Cooling : Distribution of temperature
0
54321012345
1
2
3
0
1
2
3
Horizontal air flow distance (m)
0
54321012345
1
2
3
0
1
2
3
(Strong wind : Discharge angle approx.30 ) (Room temperature approx.27 )
1.5m/s
1.0m/s
0.5m/s
0.3m/s
20
24
26
22
(Strong wind : Discharge angle approx.30 ) (Room temperature approx.27 )
SPW-XDR184GH56(A/B), X185H