4-1. Control Functions
1. Indoor Air Temprature Control
The thermostat is switched on and off in accordance with T shown below.
The frequency of the compressor's inverter is limited by either of the following controls depending on whether the
cooling or heating mode is in operation.
By the control method, not only the thermostat is switched on and off, as explained above section " 1.
Indoor air Temperature Control ", but also the frequency of the compressor's inverter is controlled in
accordance with T and fluctuations in indoor air temperature. Inverter frequency is controlled as follows:
The fluctuations of the compressor inverter frequency adjustments are calculated taking into account not only T,
but also-fluctuations in indoor air temperature.
*
* Shift Temperature
Only valid during heating operation. Set at 0 during cooling operation.
The settings at factory shipment during heating operation are as follows:
2. Compressor Frequency Control
1) Indoor Air Temperature Control
= (Indoor air temperature) - (Temperature set with the remote controller)
T
In the body thermostat mode
(setting at factory shipment)
Indoor air temperature = (Body sensor) - (Shift temperature *)
In the remote controller thermostat mode Indoor air temperature = (Remote controller sensor)
When T is high (not yet reached the temperature set
with the remote controller).
Controlled so that the inverter frequency is increased.
When T is low (approximately +1.0 or less in the
cooling mode or approximately -1.0 or more in the
heating mode).
Controlled so that the inverter frequency is decreased
or kept.
When the indoor air temperature is rising in the cooling
mode and dropping in the heating mode.
Controlled so that the inverter frequency is increased.
When the indoor air temperature is dropping in the
cooling mode and rising in the heating mode.
Controlled so that the inverter frequency is decreased.
Wall-Mounted type : 2
Floor Standing type : 0
All other types (4-way types, Concealed types, etc.) : 4
This function acts as the coefficient for adjusting differences in temperature caused by the height of the living
space from the floor to the ceiling (the temperature at ceiling height is higher) during heating operation.
The setting can be modified between 0 and 6 with mode [06] (Simple Settings Function) on the remote
controller. (Refer to the section " 7. REMOTE CONTROLLER FUNCTIONS SECTION ")
(1) Once the thermostat has been switched on, it cannot be switched off again by indoor air temperature control
for a period of 10 minutes.
(2) Once the thermostat has been switched off, it cannot be switched on again for a period of 3 minutes.
(3) The thermostat will not be switched off by indoor air temperature control and operations will continue during
the test operation mode.
Cooling Mode Heating Mode
: Thermostat ON
: Thermostat OFF
Cooling Mode :
Indoor air temperature control
Maximum and minimum frequency control
Current release control
Cooling high-load prevention control
Cooling freeze prevention control
Discharge temperature control
Heating Mode :
Indoor air temperature control
Maximum and minimum frequency control
Current release control
Heating high-load prevention control
Discharge temperature control
T
+ 1.0
- 1.0
0
T
+ 1.0
- 1.0
0
SM830161Book.indb2SM830161Book.indb2 2008/06/069:52:472008/06/069:52:47