1-3. Other Component Specifi cations
Ceiling-Mounted Type SPW-TDR184-484GH56 (A/B), T185-485H
MODEL No.
Indoor Unit
SPW-TDR184-484GH56 (A/B)
SPW-T185-485H
Power Transformer
Rated
Source VAC, Hz
Secondary
Coil resistance
Thermal cut off temperature °C
Thermistor (Coil sensor): TH
PBC-41E-AS4, PBC-41E-AS8-5
Resistance
k
–10°C: 23.7±5% 20°C: 6.5±5%
–5°C: 18.8±5% 30°C: 4.4±5%
0°C: 15.0±5% 40°C: 3.1±5%
5°C: 12.1±5% 45°C: 2.6±5%
10°C: 9.7±5% 50°C: 2.1±5%
Thermistor (Coil sensor):
KTEC-35-S98
Resistance
k
0°C: 16.5±5% 40°C: 2.7±5%
5°C: 12.8±5% 45°C: 2.2±5%
10°C: 10.0±5% 50°C: 1.8±5%
20°C: 6.3±5% 55°C: 1.5±5%
30°C: 4.0±5%
Electronic expansion valve
Valve body
Coil
Drain pump
Rated
Float switch
Rated (Contact rated)