EasyManua.ls Logo

Sanyo Big PACi 18 Series - (B) Outdoor Units

Sanyo Big PACi 18 Series
275 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-67
1
1-2. Major Component Specifi cations
(B) Outdoor Units
SPW-C706VH8
MODEL No.
SPW-C706VH8
Source
380-400-415V, 3-phase, 50/60Hz
Controller P.C.B. Ass'y
CR-C906VH8 (Microprocessor)
Control circuit fuse 20A
Compressor
Model....number C-9RVN273H0K
Source 246V (DC) / 3-phase / 60Hz (Inverter drive)
Nominal output W 4,200
Compressor oil cc 1,400
Coil resistance
(Ambient temperatur e 25°C)
C – R : 0.552 R – S : 0.552
C – S : 0.552
Safety control
Overload relay models Discharge temperature control
Operation temperature
Open °C
Close °C
Crank case heater W 25
Refrigerant amount at shipment
kg R410A - 5.3
High pressure switch
Set pressure
OFF MPa 4.15
0
– 0.15
ON MPa 3.15 ± 0.3
Fan
Number...diameter mm 2...ø490
Air circulation m
3
/ h 7,740
Fan speeds (Max.)
~860 rpm (Inverter drive control)
Fan motor
Model No. SIC-71FW-D8120
Source ~280V / 3-phase
No. of pole 8
Nominal output W 120
Safety device
Operating temperature
Open °C
Close °C
Run capacitor VAC, µF
Heat exchanger
Coil Aluminium plate fin / Copper tube
Rows...fin pitch mm 2...1.4
Face area m
2
1.27
SM830161Book.indb67SM830161Book.indb67 2008/05/1920:33:162008/05/1920:33:16