1-67
1
1-2. Major Component Specifi cations
(B) Outdoor Units
SPW-C706VH8
MODEL No.
SPW-C706VH8
Source
380-400-415V, 3-phase, 50/60Hz
Controller P.C.B. Ass'y
CR-C906VH8 (Microprocessor)
Control circuit fuse 20A
Compressor
Model....number C-9RVN273H0K
Source 246V (DC) / 3-phase / 60Hz (Inverter drive)
Nominal output W 4,200
Compressor oil cc 1,400
Coil resistance
(Ambient temperatur e 25°C)
Ω
C – R : 0.552 R – S : 0.552
C – S : 0.552
Safety control
Overload relay models Discharge temperature control
Operation temperature
Open °C –
Close °C –
Crank case heater W 25
Refrigerant amount at shipment
kg R410A - 5.3
High pressure switch
Set pressure
OFF MPa 4.15
0
– 0.15
ON MPa 3.15 ± 0.3
Fan
Number...diameter mm 2...ø490
Air circulation m
3
/ h 7,740
Fan speeds (Max.)
~860 rpm (Inverter drive control)
Fan motor
Model No. SIC-71FW-D8120
Source ~280V / 3-phase
No. of pole 8
Nominal output W 120
Safety device –
Operating temperature
Open °C –
Close °C –
Run capacitor VAC, µF –
Heat exchanger
Coil Aluminium plate fin / Copper tube
Rows...fin pitch mm 2...1.4
Face area m
2
1.27
SM830161Book.indb67SM830161Book.indb67 2008/05/1920:33:162008/05/1920:33:16