1-66
1
1-2. Major Component Specifi cations
(A) Indoor Units
Concealed-Duct High Static Pressure Type
MODEL No.
SPW-D905H
Source
220 - 230 - 240V, single-phase, 50Hz
Controller P.C.B. Ass'y
CR-UXRP71B-B (Microprocessor)
Fan (Number...diameter)
mm Centrifugal (2...ø250)
Fan motor
Model...Nominal output W KFC4X-401B3P...400 W
Power source 220 - 230 - 240V, single-phase, 50Hz
No. of pole...r.p.m. (230V, High) rpm 4P... 1,211
Coil resistance
(Ambient temperature 20°C)
Ω
BRN – WHT : 6,159 ORG – YEL : 0.87
WHT – VLT : 1.08 YEL – BLK : 2.87
VLT – ORG : 0.77 BLK – PNK : 5.98
Safety device
Operating temperature
Open °C 130 ± 5
Close °C (115 ± 5)
Run capacitor VAC, µF 450 VAC, 5.0 µF
Electronic expansion valve
Coil –
Coil resistance (at 20°C)
Ω
–
Valve body –
Heat exchanger
Coil Aluminium plate fin / Copper tube
Rows...fin pitch mm 3...2.0
Face area m
2
0.655