(5) Use shielded wires for inter-unit control wiring (c)
and ground the shield on both sides, otherwise
misoperation from noise may occur. (Fig. 1-19)
Connect wiring as shown in Section “Wiring System
Diagrams”.
X, K, T, U, D Types
XM, US Types
Fig. 1-19
WARNING
Loose wiring may cause the terminal to overheat or result
in unit malfunction. A fire hazard may also occur. Therefore,
ensure that all wiring is tightly connected.
When connecting each power wire to the terminal, follow the
instructions on “How to connect wiring to the terminal” and
fasten the wire securely with the terminal screw.
How to connect wiring to the terminal
For stranded wires
(1) Cut the wire end with cutting pliers, then strip the insulation
to expose the stranded wire about 10 mm and tightly twist
the wire ends. (Fig. 1-20)
Fig. 1-20
(2) Using a Phillips head screwdriver, remove the terminal
screw(s) on the terminal plate.
(3) Using a ring connector fastener or pliers, securely clamp
each stripped wire end with a ring pressure terminal.
(4) Put the removed terminal screw through the ring pressure
terminal and then replace and tighten the terminal screw
using a screwdriver. (Fig. 1-21)
Fig. 1-21
Shielded wire
Ground Ground
Ring
pressure
terminal
Special
washer
Screw
Terminal plate
Ring pressure
terminal
Wire
Wire
Screw and
Special washer
Ground
Ground
Shielded wire
Stranded wire
Strip 10 mm
Ring
pressure
terminal