8-20. The Self-Diagnosis Function Display and What is Detected
Alarm Display in the table below indicates the content of alarms that are displayed when a wired remote control is
connected. For information on how to deal with the alarms, refer to the Mounting Instructions for the indoor unit or to
Test Run or servicing materials.
: Off / : On / : Blinking (0.5 sec. intervals)
Error Detected
WL Remote Control LED Displa
y
Alarm Display Run Timer Standby Blinking
Communication error in the remote control
circuit
E01–E03, E08–E14, E17, E18
Communication error either in the in/
outdoor operation line or the sub-bus of
the outdoor unit
E04–E07, E15, E16, E19–E31
Operation of indoor protection device P01, P09–P14 Alternately
Operation of outdoor protection device P02–P08, P15–P31
Alternately
Error in the indoor thermistor F01–F03, F10–F11
Alternately
Error in the outdoor thermistor F04–F09, F12–F28
Alternately
Error in the indoor EEPROM F29
Simultaneously
Error in the outdoor EEPROM F30, F31
Simultaneously
Error related to the compressor H01–H31
Error in indoor settings L01–L03 L05–L09 Simultaneously
Error in outdoor settings L04, L10–L31
Simultaneously
Inconsistency in Air/Heat (Including an auto-temp setting for a model without
auto-temp settings)
Alternately
Oil Alarm (Same as operation of outdoor protection device)
Alternately
Test Run
Simultaneously
When using RCS-BH80BG.WL
If you have either an outdoor maintenance remote control or
a wired remote control and a service checker special wiring
(8540-5280-579-00: for service use) at hand, you can get more
detailed information about an alarm by connecting one to the service
connecter as in the diagram. For information such as how to connect
to receivers, etc., refer to the Users Manual that came attached with
the service checker special wiring.
Service
Connector
Fig. 8-23
Sensor Button
Fig. 8-24
8-21. Room Temperature Sensor Settings Common to All Models
●
The indoor unit and the wireless remote control are equipped with
indoor temperature sensors. The sensing of indoor temperature
works via one of them.
●
When the unit is shipped, it is set to the indoor unit, but to switch
to the remote control, press the sensor button (diagram at right)
inside the remote control’s cover and then check to make sure that
Main Sensor on the LCD screen goes off.
Even when the sensor switch has been set to the remote
control, if the unit does not receive any room temperature
data from the remote control for ten minutes, it automatically
switches back to the indoor unit sensor, so be sure to install
the remote control facing the receiver.