1-28
1
Simultaneous(Double Twin)-Type
1-1. Unit Specifi cations
Concealed-Duct Type SPW-UR184SH56B x4 / SPW-C706VH8
MODEL No.
Indoor Unit SPW-UR184SH56B x4
Outdoor Unit SPW-C706VH8
POWER SOURCE
Indoor Unit 220-230-240V, 50/60Hz, single-phase
Outdoor Unit 380-400-415V, 50/60Hz, 3-phase
PERFORMANCE
Cooling Heating
Capacity [min~max]
kW 20.0 [6.0~22.4] 22.4 [6.0~25.0]
BTU / h 68,200 [20,500~76,400] 76,400 [20,500~85,300]
Air circulation (Hi / Me / Lo) m
3
/ h 2,880 / 2,520 / 2,160 (720 / 630 / 540 x4)
Moisture removal (High) Liters / h 12.0 (3.0 x4) –
External static pressure (High) Pa (mmAg) 40 (4.1): at shipment, 62 (6.3): using the booster cable
ELECTRICAL RATINGS
Voltage ratings V 380 400 415 380 400 415
Available voltage range V 342~456(outdoor) 198~264(indoor)
Running amperes* A 10.5 10.1 9.8 10.3 10.0 9.7
Max–Running amperes** A – – – – – –
Power input kW 6.52 6.54 6.57 6.44 6.47 6.50
C.O.P W / W 3.07 3.06 3.04 3.48 3.46 3.45
Max.Starting amperes A – – – – – –
FEATURES
Controls / Thermostat control Microprocessor / I.C.thermostat
Timer ON / OFF 72-hours
Fan speeds Indoor / Outdoor 3 and Automatic control / Variable
Airflow direction (Indoor) –
Air filter Field supply
Remote controller (Option) Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL
Refrigerant control –
Drain pump (Drain connection) Max.head 50cm above drain connection (25A, OD32mm)
Compressor Rotary (SANYO)
Operation sound
Indoor - Hi / Me / Lo
dB-A 30 / 28 / 25, (33 / 30 / 28: using the booster cable)
Outdoor - Hi dB-A 57 57
Color
(Approximate value)
Indoor –
Outdoor Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Indoor unit Outdoor unit
Limit of tubing length m (ft.) 100 (328)
Limit of tubing length at shipment m (ft.) 5~30(16~98)
Limit of elevation difference
between the two units
m (ft.)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 30 (98)
Refrigerant tube
outer diameter
Liquid tube mm (in.) 6.35 (1 / 4) 9.52 (3 / 8)
Gas tube mm (in.) 12.7 (1 / 2) 25.4 (1)*
1
Refrigerant amount at shipment kg – R410A - 5.3
DIMENSIONS & WEIGHT
Indoor unit Outdoor unit
Unit dimensions
Height mm (in.) 310 (12-7 / 32) 1526 (60-5 / 64)
Width mm (in.) 700 (27-9 / 16) 940 (37-1 / 64)
Depth mm (in.) 686 (27) 340 (13-25 / 64)
Package dimensions
Height mm (in.) 325 (12-25 / 32) 1676 (65-63 / 64)
Width mm (in.) 975 (38-3 / 8) 1076 (42-23 / 64)
Depth mm (in.) 778 (30-5 / 8) 420 (16-17 / 32)
Net weight kg (lb.) 25 (55) 118 (260)
Shipping weight kg (lb.) 29 (64) 128 (282)
Shipping volume m
3
(cu.ft) 0.247 (8.9) 0.757 (26.7)
NOTE
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
*1 There are two types of supplied tubings. The one tubing port ø19.05 (fl are process) is connected to the fl ared connection of the gas port
side’s service valve. The other “L” shaped tubing port is brazed in connection after cutting the tube at the proper length.
Then make a brazing connection to the main tubing (ø25.4).
Cooling:
Rating conditions (*): Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**): Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*): Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**): Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
SM830161Book.indb28SM830161Book.indb28 2008/05/1920:33:022008/05/1920:33:02