EasyManua.ls Logo

Sanyo Big PACi 18 Series - Page 75

Sanyo Big PACi 18 Series
275 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-70
1
1-3. Other Component Specifi cations
4-Way Air Discharge Semi-Concealed Type SPW-XM185H
MODEL No.
Indoor Unit SPW-XM185H
Power Transformer
Rated
Source VAC, Hz
Secondary
Coil resistance
Thermal cut off temperature °C
Thermistor (Coil sensor): TH
PB2M-41E-S15-1
Resistance
k
–10°C: 23.7±5% 20°C: 6.5±5%
–5°C: 18.8±5% 30°C: 4.4±5%
0°C: 15.0±5% 40°C: 3.1±5%
5°C: 12.1±5% 45°C: 2.6±5%
10°C: 9.7±5% 50°C: 2.1±5%
Thermistor (Coil sensor):
KTEC-35-S98
Resistance
k
0°C: 16.5±5% 40°C: 2.7±5%
5°C: 12.8±5% 45°C: 2.2±5%
10°C: 10.0±5% 50°C: 1.8±5%
20°C: 6.3±5% 55°C: 1.5±5%
30°C: 4.0±5%
Electronic expansion valve
Valve body
Coil
Drain pump
PLD-12230ST-2
Rated
AC 230V, 12W
Float switch
FS-0218-102
Rated (Contact rated)
Contact open at float rising
SM830161Book.indb70SM830161Book.indb70 2008/05/219:20:562008/05/219:20:56

Table of Contents

Related product manuals