EasyManua.ls Logo

Sanyo SAP–K181AHA–S - Outdoor Unit

Sanyo SAP–K181AHA–S
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
2-2-2. Outdoor Unit
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Controller PCB POWC186GH
Type Rotary (Hermetic)
Compressor model C2R170H5T 80827445
Nominal output W 1,700
Compressor oil ... Amount cc 4GSDT or SAY-56T ... 750
Coil resistance (Ambient temp. 25°C) C – R : 1.35
C – S : 3.42
Type Internal protector
Safety
Overload relay
devices Operating temp. Open °C 170 ± 5
Close °C 105 ± 11
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 40 A
Run capacitor µF 40.0
VAC 400
Crank case heater 240V 30W
Type Propeller
Q´ty ... Dia. mm 1 ... ø 420
Fan motor model ... Q´ty KFG6S51A5PAS ... 1
No. of poles ... rpm (240 V, High) 6 ... 880
Nominal output W 50
Coil resistance (Ambient temp. 20°C) WHT – BRN : 67.1
WHT – YEL : 68.1
YEL – PNK : 15.7
Safety
Type Thermal protector
devices Operating temp. Open °C 130 ± 8
Close Automatic reclosing
Run capacitor µF 4.0
VAC 440
Coil Aluminum plate fin / Copper tube
Rows 1
Fin pitch mm 1.4
Face area m
2
0.485
External Finish Acrylic baked-on enamel finish
Heat
Exch. Coil
CompressorFan & Fan Motor
Outdoor Unit SAPC181AHA

Table of Contents