EasyManua.ls Logo

Sanyo SAP–K181AHA–S - Defrosting Operation

Sanyo SAP–K181AHA–S
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8-7. Defrosting Operation (Heating)
Defrosting Flowchart
Compressor ON
Indoor heat exchanger coil
temperature drops 0.8°C per
6 minutes and it repeats
3 times in succession.
Integrated operating time of
compressor is more than 3
hours.
Defrosting begins.
Cold-draft prevention
Temperature of outdoor heat
exchange coil is higher than
12°C.
Release of defrosting
Indoor fan runs at set speed
when temperature of indoor
heat exchanger reads 35°C.
B
Defrosting time is over 12
minutes.
No LL fan operation during this period.
Compressor keeps running
for at least 6 minutes.
Temperature of outdoor heat
exchanger coil is below 9°C.
Integrated operating time of
compressor is more than 1.5
hours.
Thermo. OFF.
(Compressor OFF)
C D
Temperature of indoor heat
exchanger coil is below 45°C.
Continuous operating time of
compressor is more than 20
minutes.
Outdoor fan is either operated
or stopped for more than 10
minutes.
A
Is outdoor fan continuously
operating for more than 10
minutes?
Integrated operating time of
compressor is more than 50
minutes.
Temperature of indoor heat
exchanger coil is below 45 +
13°C.
Temp. of indoor heat exch.
coil immediately before thermo
goes off is either below 45 + 4°C
or 58 + 4°C (when overload
prevention works).
NO
NO
NO
YES
YES
YES
Overload
prevention works.
Does outdoor fan
stop?
Compressor keeps running for
at least 6 minutes.
Release of overload prevention
(Outdoor fan operates.)
Compressor keeps running for
at least 6 minutes.
NOTE
34

Table of Contents

Related product manuals