4. REFRIGERANT FLOW DIAGRAM
12
Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min. 8 mm.
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
IMPORTANT
Wide tube
Thickness:
Min. 8 mm
Insulation
Narrow tube
Thickness:
Min. 8 mm
Indoor Unit SAPK181AHA Outdoor Unit SAPC181AHA
4-way
valve
Accumulator
Wide tube
service
valve
Wide tube
O.D.
ø12.7 mm
(1/2 ")
Compressor
Narrow
tube
service
valve
Narrow tube
O.D.
ø6.35 mm
(1/4")
Heat exchanger
Cooling cycle
Heating cycle
Strainer
Strainer
Indoor unit Outdoor unit
Heat exchanger
Capillary
tube
Capillary for
liquid injection
Indoor Unit SAPK241AHA Outdoor Unit SAPC241AHA
4-way
valve
Accumulator
Wide tube
service
valve
Wide tube
O.D.
ø15.88 mm
(5/8 ")
Compressor
Narrow
tube
service
valve
Narrow tube
O.D.
ø6.35 mm
(1/4")
Cooling cycle
Heating cycle
Strainer
Strainer
Indoor unit Outdoor unit
Heat exchanger
Capillary
tube
Capillary for
liquid injection
Muffler
Heat exchanger