9-3. Some part of air conditioner does not operate.
9-3-1. Only indoor fan does not run.
9-3-2. Only flap motor does not run.
9-3-3. Function of outdoor fan speed control does not work properly.
Check thermostat in outdoor unit.
(23S)
Refer to "8-8 Outdoor Fan Speed Control".
Measure resistance of flap motor
winding.
Fan cannot
be turned.
OK
Check fan rotation.
Turn fan gently once or twice by
hand.
Check fan casing
foreign matter on
inside.
Fan motor burnout
or foreign matter in
bearings.
Remove foreign
matter or repair.
Repair or replace.
Measure resistance of indoor fan
motor winding.
Check fan motor capacitor.
OK
Measure resistance of indoor fan
motor winding.
Check fan motor capacitor.
NO
When fan speed is changed, does
applied voltage between lead wires
BRN and WHT change as well ?
PCB Ass'y is defective.