9-2-3. Only outdoor unit does not run.
A. Check setting temperature.
B. Check either power relay or magnetic contactor in outdoor unit.
Check indoor PCB Ass'y.
Check coil terminal voltage between
terminals A1 and A2 at magnetic
contactor. (AC 220 - 240 V)
No voltage appears.
OK
Check voltage between terminals
No. 2 and No. 3 at terminal plate.
(AC 220 - 240 V)
OK
For 224 class model
Check coil resistance of magnetic
contactor.
OK
Replace the magnetic contactor.
Check indoor PCB Ass'y.
Check coil terminal voltage between
terminals No. 5 and No. 6 at power
relay. (AC 220 - 240 V)
No voltage appears.
OK
Check voltage between terminals
No. 2 and No. 3 at terminal plate.
(AC 220 - 240 V)
OK
For 184 class model
Replace the power relay.
NO
Is room temperature too low ?
Try to lower setting temperature by
temperature setting button ( button).
Outdoor unit still does
not run.
Check to see if inter-unit wiring is
correctly connected between indoor
and outdoor unit.
Check to see if inter-unit wiring is
correctly connected between indoor
and outdoor unit.
COOL
NO
Is room temperature too high ?
Try to raise setting temperature by
temperature setting button ( button).
Outdoor unit still does
not run.
HEAT