9-4. Air conditioner operates, but abnormalities are observed.
9-4-1. Operation does not switch from HEAT to COOL (or COOL to HEAT).
Indoor PCB Ass'y is defective.
Check voltage between terminals
No.2 and No.5 at the terminal plate.
(AC 220 - 240V)
No voltage appears.
Remote control unit may be defective.
Measure resistance of 4–way valve's
winding.
Receiver in lamp Ass'y may be
defective.
COOL HEAT
Check voltage between terminals
No.2 and No.5 at the terminal plate.
(0V)
HEAT COOL
Check to see if switching sound (click)
is heard from 4–way valve's body.