Appendix B Standards Compliance
150 EM13x Series SMART MULTIFUNCTION METER
Measurement Specifications
Table 23: Measurement Specifications Parameters
120VxPT @ 120V
400VxPT @ 690V
0 to 1,150,000 V
Starting voltage
1.5-5.0% FS (selectable)
Voltage, V
(EM133-SE model)
80 to 1,150,000 V
Starting voltage 80VAC
(w/1phase)
For In = 5A
1% to 200% FS
For In = 1A
2% to 200% FS
0.36PTCT @ 120V
1.2PTCT @ 690V
34.5 @(230V,50A)
-10,000,000 kW to
+10,000,000 kW
0.36PTCT@ 120V
1.2PTCT @ 690V
34.5 @(230V,50A)
-10,000,000 kvar to
+10,000,000 kvar
0.36PTCT @ 120V
1.2PTCT @ 690V
34.5 @(230V,50A)
15 Hz to 70 Hz
15 Hz to 70 Hz
15 Hz to 70 Hz
320 Hz to 480 Hz
Total Harmonic
Distortion, THD
V(I), %V
f
(%I
f
)
THD 1%,
V 10% FSV and
V
L-N
> 25V,
I 10% FSI
Total Demand
Distortion, TDD, %
TDD 1%,
I 10% FSI,
V
L-N
> 25V
Active energy
Import & Export
Class C as per EN50470-3, Class
0.5S under conditions as per
IEC/AZ 62053-22:2003 at 50/60 Hz
& ANSI C12.20 Ac. Class 0.5
Reactive energy
Import & Export
Class 0.5S under conditions as per
IEC 62053-22:2003, |PF| 0.9 and
at 50/60 Hz
Class 0.5S under conditions as per
IEC 62053-22:2003 at 50/60 Hz
PT - external potential transformer ratio
CT - primary current rating of the external current transformer
FSV - voltage full scale
FSI - current full scale
V
f
- fundamental voltage
I
f
- fundamental current
@ 80% to 120% of voltage FS, 1% to 200% of current FS at (In = 5 and 1 A), 2% to 200% of
current FS 50 A and frequency 50/60 Hz