Chapter 5 Configuring the EM13X Series General Meter Setup
EM13x Series SMART MULTIFUNCTION METER 95
setpoint alarm status until it is explicitly cleared through
communications or via the display.
A programmable action is performed on setpoint status transition
when a setpoint event is asserted.
Generally, setpoint actions are performed independently for each
setpoint and can be repeated a number of times for the same target.
The exceptions are relay operations that are shared for each target
relay between all setpoints using an OR scheme.
A relay output is operated when one of the setpoints linked to the relay
is activated and remains operated until all of these setpoints are
released (except for latched relays that require a separate release
command to be deactivated).
Using Time Counters
Any of the general counters can be used to count the setpoint
operation time. If you select the TIME CNT n action for a setpoint, the
target counter measures the time while the setpoint is in the operated
state. The counter resolution is 0.1 hour. See Status Display in Chapter
3 on how to examine the counters via the front display.