EasyManua.ls Logo

sauter NRT405F901 - BACnet Multistate Values and Device Objects

sauter NRT405F901
50 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NRT405F901 manual Chapter 19 BACnet signals 47
Multistate values
Object name Object ID Description Values Writeable
RC_Setp_X.NRTHeatOutputSelect Multistate value, 0 Manual/Auto
heat output
1=Off
2=Manual output
3=Automatic output
Yes
RC_Setp_X.NRTCoolOutputSelect Multistate value, 1 Manual/Auto
cool output
1=Off
2=Manual output
3=Automatic output
Yes
RC_Setp_X.NRTFanSelect Multistate value, 2 Fan mode select 1=Off
2=Manual speed 1
3=Manual speed 2
4=Manual speed 3
5=Auto
6=Auto 2
7=Auto 1
Yes
Not used in this model Multistate value, 3 Manual/Auto
forced ventilation
1=Off
2=Manual on
3=Auto
Yes
RC_Setp_X.NRTChangeOverSelect Multistate value, 4 Manual/Auto
change-over
1=Heating
2=Cooling
3=Auto
Yes
RC_Setp_X.NRTRemoteState Multistate value, 5 Remote control
unit state
1=Off
2=Economy/Standby
3=Economy/ Standby
4=Presence
6=No remote control
Yes
Device
The Device object contains to writeable properties; Description and Location. Description
can be 17 characters in length and Location can be 33 characters, as long as single byte
character encoding is used.