How to test the alarm system
ATTENTION: You must stop or slow down the engine during this test! Before starting the
test, perform procedure 1 and 2 of the maintenance schedule for your system. The pipe
system must be clean and if used siphons to be filled with oil!
It is important to test your oil mist system regularly during maintenance
work and replacement of measuring head or complete oil mist detector.
It is important to ensure that the oil mist detector works according to the
functionality instructions and that the alarm signal from the oil mist
detector reaches the shutdown/reduced RPM function at the engine
during an alarm situation!
How to perform the test:
To perform the functionality test, we offer you the “Test plate kit for functional test of Oil Mist Detector” (Part no.: 11072).
The kit contains a test plate and a test glass 10%.
Below are step-by-step instructions of how to perform the test.
For more information and different test guides:
https://www.epp.no/maintenance/

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Schaller Automation VN/87 EMC Series and is the answer not in the manual?

Schaller Automation VN/87 EMC Series Specifications

General IconGeneral
BrandSchaller Automation
ModelVN/87 EMC Series
CategorySecurity Sensors
LanguageEnglish

Related product manuals