Pag. 34-EN UMT/WG T BT Rev3.0 – 08/10/2021
- wrong parameters values or inadequate
motor.
The temperature detected by the PTC
thermistor corresponds to a resistance >
2600 ohm.
Reduce the motor load.
Check motor cooling.
Reserved (for future
use)
Execution of reset parameter default
command;
Parameters user setting corrupted
Input power supply phase loss, three-phase
power supply unbalance
Check the input power supply phases to the
drive, reduce motor power (speed)
Check the serial connection. Switch the drive
off and back on again.
Check the parameter values
Restart the command again
Driver disabled (STO
input open or de-
energized)
Cable disconnected
Operation of external contactor
24V power supply loss
Check the wiring.
Restore external contactor
Check the connections of the motor cable
Reserved (for future
use)
Wrong parameters values or unsuited load
Switch the drive off and back on again and
check the parameters are properly set. Check
the motor load.
Too high power supply voltage
Check input power supply and if inductive
load generating overvoltage are connected to
the line
Power supply
undervoltage
Too low power supply voltage
Reserved (for future
use)
The drive has detected a ground current too
high
Check ground insulation of the motor and
wires .
The current supplied has exceeded the drive
rated current over the maximum time
accepted
Check the load, the dimension of the motor
and the cables. Check the motor parameters.