Power Socket Test
Input voltage range: 195 V ... 253 V
AC
Testing of voltage potential:
- U (L-PE)
- U (N-PE)
- U (L-N)
Displayed measured value: U (L-N)
RCD Test
Test Voltage:
Test Current:
Test Current Accuracy:
Display Range:
Measurement Range:
Resolution:
Operating Error:
230 V +10 %, –15 %
30 mA / 150 mA rms sinusoidal
30 mA –10 % +0 %, 150 mA +10 %, –0 %
0 ms … 2000 ms
1 ms … 2000 ms
1 ms
±1 ms
External Leakage Current (Adapter 3~)
Test Voltage:
Display Range:
Measurement Range:
Resolution:
Operating Error:
Connected to External Adapter
0 mA … 9.00 mA
0.25 mA … 9.00 mA
0.01 mA
±5 % of reading ±2 digits