11
The condenser fan is synchronized with the compressor operation, in particular providing the option to set
start and stop delays in relation to the thermostat status.
Furthermore, it is possible to continuously run the condenser fan (forced ON operation).
It is possible to detect some condenser fan defects.
Condenser fan
Settings
Measurement
10.
CONDENSER FAN
Name Default Max value Min value Step Unit
Fan start delay 0 240 0 1 Seconds
Fan stop delay 0 240 0 1 Seconds
Fan forced ON OFF ON OFF 1
Detect missing fan OFF ON OFF 1
Name Description Step Unit
Fan speed Actual fan speed 0/100 %