BATTERY PROTECTION
Battery Protection
Settings
Measurements
In order to avoid permanent damage to the battery, due to discharge, there must be a battery protection.
The setting range is from 8.5 to 17 V DC.
A critical stop without delay occurs if the voltage drops below 7 V DC or exceeds 17V DC.
Tolerances are ± 0.15 V DC.
Name Default Max value Min value Step Unit
Battery cut out level 8.5 17 8.5 0.1 Volt
Battery cut in diff. 0.5 8 0.5 0.1 Volt
Cut out delay 3 60 0 1 Seconds
Name Description Step Unit
Cut in level Calculated value. Cut in = Cut out + Diff 0.1 Volt
Supply voltage Actual voltage measured on + & - terminals 0.1 Volt