GC1100 SEDEMAC
Page | 7
2.8 Analog Current Input
Following table gives a brief overview of analog current input
Table 11: Analog voltage/current input
Controller's terminal number
23
Type
current sensing
Range
4 to 20 mA
Accuracy
±1.25% of full scale
Resolution
0.1mA
2.9 Magnetic Pick Up Input
Following table gives a brief overview of magnetic pickup input
Table 12: Magnetic pickup input
Controller's terminal number
42
Type
Single ended
Frequency range
10 to 10000 Hz
Input voltage range
200 mV to 45 V-AC RMS
The Magnetic Pick Up (MPU) is an inductive sensor fitted on the engine flywheel for the engine
speed sensing. The output of MPU is a sine-wave signal.
2.10 Digital Outputs
Following table gives a brief overview of digital outputs
Table 13: Digital outputs
Controller's terminal number
3, 4, 5, 6, 8, 9
Number of outputs
6
Type
High side driver
Maximum current
0.75 A
Software configurable options
Start relay, Fuel relay and many more. Refer Table 26
Do not connect “STARTER MOTORand “STOP SOLENOIDdirectly to the
controller's output terminals
Genset & mains contactor latching relays should be compiled against 4kVA surge as
per IEC-61000-4-5 standard.