Page | 48
Register
Address
Parameter
Scale Factor
Unit/Interpretation
Bits/ Sign
63
Mains run min
1
Min
Unsigned
64
Alarm 1
Low oil pressure
--
--
13/16-16/16
High coolant temperature
--
--
9/16-12/16
Low fuel level
--
--
5/16-8/16
Water level switch
--
--
1/16-4/16
65
Alarm 2
Under speed
--
--
13/16-16/16
Over speed
--
--
9/16-12/16
Fail to start
--
--
5/16-8/16
Fail to stop
--
--
1/16-4/16
66
Alarm 3
Reserved
--
--
13/16-16/16
Reserved
--
--
9/16-12/16
Generator low frequency
--
--
5/16-8/16
Generator high frequency
--
--
1/16-4/16
67
Alarm 4
Generator high current
--
--
13/16-16/16
Generator overload
--
--
9/16-12/16
Unbalanced load
--
--
5/16-8/16
Emergency stop
--
--
1/16-4/16
68
Alarm 5
Charge alternator failure
--
--
13/16-16/16
Maintenance
--
--
9/16-12/16
Reserved
--
--
5/16-8/16
Reserved
--
--
1/16-4/16
69
Alarm 6
Battery low voltage
--
--
13/16-16/16
Battery high voltage
--
--
9/16-12/16
Temperature Circuit open
--
--
5/16-8/16
Reserved
--
--
1/16-4/16
70
Alarm 7
Fuel theft
--
--
13/16-16/16
Magnetic pick up fault
--
--
9/16-12/16
Oil pressure Open circuit
--
--
5/16-8/16
Auxiliary input i
--
--
1/16-4/16
71
Alarm 8
Auxiliary input a
--
--
13/16-16/16
Auxiliary input b
--
--
9/16-12/16
Auxiliary input c
--
--
5/16-8/16
Auxiliary input d
--
--
1/16-4/16