Nominal AC Voltage | 120/240 Vac |
---|---|
Nominal DC Voltage | 125/250 Vdc |
Current Rating | Up to 5 A |
Frequency | 50/60 Hz |
Trip Coil Current | User-configurable |
Protection Functions | Overload, Short Circuit, Ground Fault |
Communication Protocols | DNP3 |
Operating Temperature | -40 to +85 °C |
Diagram of default I/O assignments for feeder protection using the SEL-849 relay.
Connect computer to PORT2A or PORT2B of the relay using an Ethernet cable.
Open an Internet browser and type the SEL-849 default IP address (169.254.0.1).
Select Access Level, enter default passwords (OTTER/TAIL) and click Login.
Set rated frequency, phase rotation, and application type (FEEDER).
Set Phase CT Ratio (CTR1) and Full Load Amps (FLA1) based on feeder and CT specifications.
Ensure Factory Logic (FACTLOG) is set to Y in Configuration Settings.
Set instantaneous overcurrent pickup and delay for phase and residual faults.
Set time-overcurrent pickup, curve, and time dial for phase and residual faults.
Verify settings and submit changes to apply the basic feeder protection configuration.