EasyManua.ls Logo

Seneca KEY Series - Gateway Configuration; Gateway Configuration with the Webserver for the Copadata Iec61850 Client Client

Seneca KEY Series
34 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
User Manual
IEC 61850 MODBUS
GATEWAYS
ALL RIGHTS RESERVED. NO PART OF THIS PUBLICATION MAY
BE REPRODUCED WITHOUT PRIOR PERMISSION.
www.seneca.it
MI00705-0-EN
GATEWAY CONFIGURATION
GATEWAY CONFIGURATION WITH THE WEBSERVER FOR THE “COPADATA IEC61850
CLIENT™” CLIENT
The COPADATA “IEC61850 Client” software will be used as IEC 61850 client for Windows.
For more information on the client software, refer to:
https://www.copadata.com
The purpose is to configure the gateway so that it can read a register coming from the serial modbus RTU
protocol from a 61850 client.
We configure the Gateway via the webserver, first we activate the webserver (by default the device is in
IEC61850 mode), we hold down the side button until the device restarts.
At this point the PWR LED starts to flash to indicate the operating mode as a webserver for the configuration.
The default address of the webserver is:
http://192.168.90.101
user: admin
password: admin

Related product manuals