Switched PRO2 User Guide
Using the Command Line Interface (CLI) 154
set branch
Sets branch configuration values.
Command Syntax
set branch email [disabled | enabled] <name | id | ALL>
set branch load [alarmhi | alarmlo | warnhi | warnlow] <name | id | ALL> <value>
set branch load hyst <value>
set branch snmpt [disabled | enabled] <name | id | ALL>
Parameters
The set branch command uses the following parameters:
email
Email notifications for branch events.
hyst
Hysteresis between event state and recovery (0.0 to 10.0).
load
Current load for a branch.
min=0A; max (max current) in show branches command; hyst=0.0-10.0A;
default-1.0A.
snmpt
SNMP trap notifications for branch events.
Sub Parameters
The set branch command uses the following sub-parameters:
alarmhi
High alarm value.
alarmlo
Low alarm value.
warnhi
High warning alarm.
warnlo
Low warning alarm.
Usage Guidelines
min <= alarmlo <= warnlo <= warnhi <= alarmhi <= max
Command Access
Admin level only