Using the Command Line Interface (CLI) 199
show units
Shows CDU configuration values.
Command Syntax
show units
Command Access
Admin level only
Example
Switched CDU: show units
Unit Name: Master <A>
Type: Master
Model Number: STV-6503K
Product S/N: STVU0000118
Asset Tag: testtag1asdf
Display Orient: Auto <Normal>
Outlet Sequence: Normal
SNMP Notif.: enabled
Email Notif.: enabled
Unit Name: Link <B>
Type: Link
Model Number: SEV-4503K
Product S/N: <not set>
Asset Tag: AGHWERAFSasdf
Display Orient: Auto <Normal>
Outlet Sequence: Normal
SNMP Notif.: enabled
Email Notif: enabled
show ups
Shows UPS device configuration values.
Command Syntax
show ups
Command Access
Admin level only
Example
Switched CDU: show ups
UPS #1: Generic RFC1628
SNMP Host/IP: (not set)
SNMP Port: 161
SNMP Get Community: public
SNMP Status OID: .1.3.6.1.2.1.33.1.4.1.0
SNMP On Utility Val: 0x3
SNMP On Battery Val: 0x5
Line List: