Switched PDU
Installation and Operations Manual Operations 55
Administrative Command Summary (continued…)
Set Location Specifies a descriptive field for the Web control screen and login banner
Set Net Determines the acquisition method for the protocol stack and IPv4/IPv6 addresses
Set Option Button Enables or disables the external configuration reset button
Set Option Coldboot Alert Enables or disables the Coldboot Alert feature using a serial protocol
Set Option Display Sets the LED orientation for external Current displays
Set Option More Enables or disables the ‘more’ prompt
Set Option Outlet Sequence Configures outlet power-on sequence order as normal or reversed
Set Option Prompt Configures a custom CLI prompt
Set Option Startupstick Enables or disables the StartUp Stick tool for PDU mass configuration
Set Option StrongPasswords Enables or disables strong password requirements
Set Option Tempscale Sets the Environmental Monitor temperature scale
Set Option CLI Timeout Sets the Command Line Interface (CLI) session timeout period
Set Option Web Timeout Sets the web session (Web Interface) timeout period
Set Outlet Locked Locks or unlocks a single outlet (no control) in its current state
Set Outlet Name Specifies a descriptive field for a device attached to an outlet
Set Outlet PostOnDelay Sets the Post-On delay for an outlet
Set Outlet RebootDelay Sets the reboot delay for all outlets
Set Outlet SeqInterval Sets the sequencing interval for all outlets
Set Outlet Wakeup Sets the wakeup state for an outlet
Set Port CLI Enables or disables availability of the Command Line Interface (CLI)
Set Port DSR Check Sets the DSR active signal checking for a serial/Pass-Thru port
Set Port Name Specifies a descriptive field for a serial/Pass-Thru port
Set Port SCP Enables or disables Serial Command Protocol (SCP) functions
Set Port SCP Emulate Notifies the Serial Command Protocol (SCP) of an MRV device on a specific serial port
Set Port Speed Set the connection speed for all serial/Pass-Thru ports
Set Port Timeout Sets the inactivity timeout period for a serial port before closing the pass-thru session
Set Port RFTag Enables or disables RF Code sensor tags for the wireless monitoring solution
Set SCPAuth Enables or disables Serial Command Protocol (SCP) authentication
Set SCPAuth User Sets the username and password for Serial Command Protocol (SCP) authentication
Set SNMP IP Restrict Allows SNMP Get and Set requests only from defined trap destinations
Set SNTP Sets the IP address or hostname of the SNTP servers
Set SNTP DST Enables or disables Daylight Saving Time (DST)
Set SNTP DST End Specifies settings for Daylight Saving Time (DST) day/time end parameters
Set SNTP DST Start Specifies settings for Daylight Saving Time (DST) day/time start parameters
Set SNTP GMTOffset Sets the local GMT offset applied to the SNTP date/time
Set SPM Enables/disables secure access of Sentry Power Manager (SPM)
Set SPM Reset Password Resets the SPM password on the PDU to its internal default password
Set Subnet Sets the subnet mask of the PDU
Set System Area Specifies to total system area for the system
Set System Area Unit Specifies the system area (footprint) unit of measure
Set System Balance Sets the percentage as load out-of-balance threshold for 3-phase systems
Set System Balance Alert Enables/disables alert when load out-of-balance threshold is reached for 3-phase systems
Set System PF Sets the power factor used in the total system power calculation
Set Telnet Port Sets the Telnet server port number
Set Telnet Enables or disables Telnet access