80 Operations Switched PDU
Installation and Operations Manual
To enable or disable coldboot alert:
Upon a coldboot of the system (if the Coldboot Alert feature is enabled), the system sends a ½ second RS-232 break
out on any serial ports that are also enabled.
The Set Option Coldboot Alert command enables or disables the Coldboot Alert feature.
To enable or disable coldboot alert:
At the Switched CDU: prompt, type set option cbalert, followed by enabled or disabled, and press Enter.
To enable or disable the Serial Command Protocol (SCP) authentication:
The Set SCP Authentication command enables or disables SCP Authentication.
To enable or disable SCP:
At the Switched CDU: prompt, type set scpauth, followed by enabled or disabled, and press Enter.
To set the Serial Command Protocol (SCP) authentication user:
The Set SCPAuth User command sets the username and password for SCPAuthentication.
To set SCP username:
At the Switched CDU: prompt, type set scpauth user, followed by user name, and press Enter. You will be
prompted to enter and verify a password.
Displaying system options:
The Show Options command displays settings for all system options.
To display system option information:
At the Switched CDU: prompt, type show options and press Enter.
Example
Switched CDU: show options
System Options
Display Orientation: Auto <Normal>
Outlet Sequence Order: Normal
Strong Passwords: Disabled
Configuration Reset Button: Enabled
More Prompt: Enabled
Temperature Scale: Celsius
CLI Custom Prompt: <none>
CLI Session Timeout: 10 minutes
Web Session Timeout: 10 minutes
Coldboot Alert <SCP>: Enabled
StartUp Stick: Enabled
NOTE: The display of “<SCP>” after the Coldboot Alert parameter in the Show Options command (as indicated above) shows a
relationship between the Serial Command Protocol (SCP) and the Coldboot Alert feature. Upon a coldboot of the system, if the Coldboot
Alert feature is enabled, the system will send a ½ second RS-232 break out to to any SCP-enabled serial ports.
Displaying the firmware version:
The Version command displays the firmware version.
To display the firmware version:
At the Switched CDU: prompt, type version and press Enter.
Performing a warm boot:
The Restart command performs a warm boot of the PDU.
NOTE: System user/outlet/group/port configuration or outlet states are not changed or reset with the Restart command.
To perform a warm boot:
At the Switched CDU: prompt, type restart and press Enter.